The DSE 6020 MKII is an Auto Mains (Utility) Failure Control Module developed to provide a wide range of operating and monitoring features for single diesel and gas gen-sets.
OVERALL SIZE
216 mm x 158 mm x 43 mm (8.5” x 6.2” x 1.5”)
PANEL CUTOUT SIZE
184 mm x 137 mm (7.2″ x 5.3″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.48kg
PRODUCT VARIANTS
6020-03 – MKII Auto Mains (Utility) Failure Control Module
6020-04 – MKII Auto Mains (Utility) Failure Control Module (Htr)
KEY FEATURES | KEY BENEFITS |
Support for 0-10 V & 4-20mA oil pressure senders. | Provides flexibility for use with multiple sensors and engine types. |
Large back-lit icon LCD display. | Displays information to the operator in a clear and concise format. |
Heated display option. | Ensures the display continues to operate in extreme cold weather conditions. |
3-phase generator sensing. | Provides true generator sensing. |
3-phase generator and mains (utility) sensing. | Provides true generator and mains (utility) sensing. |
Breaker control buttons on front fascia. | Instant breaker control when working with a control module. |
Generator & load power monitoring (kW, kV A, kV Ar, pf). | Provides clear accurate power measurement information. |
Generator overload protection (kW). | Provides clear and easy to read information pages. |
Generator/load current monitoring & protection. | Provides convenience of monitoring and protection of the generator or monitoring of the load current. |
Configurable analogue/digital inputs. | Provides multiple installation options. |
Configurable DC, volt-free and staged loading outputs. | Provides full generator load control. |
CAN, MPU & alternator speed sensing (selectable depending on engine type). | Makes the module ideal for standard and electronic engine applications. |
Tier 4 CAN engine support. | Ensures the control module can be used with the latest in modern electronic engine technology. |
Configurable event log (50). | Provides access to historical alarms and operational status. |
DSE Configuration Suite PC Software. | Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring. |
Fuel and start outputs (configurable on CAN). | Provides multiple installation options. |
ADDITIONAL FEATURES |
Engine maintenance alarms (3). |
Engine speed protection. |
Engine hours counter. |
Engine pre-heat. |
Engine run time scheduler. |
Engine idle control for start/stop. |
Manual fuel pump control. |
Backed-up real time clock. |
Battery voltage monitoring. |
Start on low battery. |
Configurable remote start input. |
Alternative configuration (1). |
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
100 mA at 12 V, 105 mA at 24 V
MAXIMUM STANDBY CURRENT
60 mA at 12 V, 55 mA at 24 V
MAXIMUM SLEEP CURRENT
40 mA at 12 V, 35 mA at 24 V
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
DIGITAL INPUTS A to F
Negative switching
ANALOGUE INPUTS A to C
Configurable as:
Negative switching digital input
0 Ω to 480 Ω
ANALOGUE INPUT D
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 480 Ω
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
AUXILIARY OUTPUTS C, D, E & F
2 A DC at supply voltage
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.