The DSE6120 MKIII is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single, diesel or gas, genset applications.
Monitoring an extensive number of engine parameters, the module will display warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LEDs and remote PC.
The module is compatible with electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engines and offers an extensive number of flexible inputs, outputs and extensive engine protections so the system can be easily adapted to meet the most demanding industry requirements.
The extensive list of features includes enhanced event and performance monitoring, remote communications & PLC functionality. The modules can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available.
OVERALL SIZE
216 mm x 158 mm x 43 mm (8.5” x 6.2” x 1.5”)
PANEL CUTOUT SIZE
184 mm x 137 mm (7.2” x 5.3”)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.5kg
PRODUCT VARIANTS
6120-05 – 6120 MKIII Auto Mains (Utility) Failure Control Module
KEY FEATURES | KEY BENEFITS |
6 configurable DC outputs. | Provides multiple installation options. |
4 configurable analogue/digital inputs. | Provides multiple installation options. |
8 configurable digital inputs. | Provides multiple installation options. |
3-phase generator and mains (utility) sensing. | Provides true generator and mains (utility) sensing. |
Automatic load transfer control. | Ensures the load can be transferred manually/automatically between mains (utility) and generator power. |
Generator & mains current and power monitoring. | Provides convenience of monitoring and protection of the generator or monitoring of the load current. |
Internal PLC editor. | Adds increased flexibility to the product. |
Breaker control buttons on front fascia. | Simple breaker control at the touch of a button. |
Fuel and start outputs configurable when using CAN. | Provides multiple installation options. |
Tier 4 ECO engine support including exhaust fluids & filters. | Ensures the control module can be used with the latest in modern electronic engine technology. |
DSENet expansion compatibility. | Offers optimum flexibility for system expansion. |
Data logging facility | Data can be used for gathering system information. |
Configurable event log (100). | Provides access to historical alarms and operational status. |
CAN, MPU & alternator speed sensing (selectable depending on engine type). | Ensures the module can be used with a wide number of engine types. |
Support for 0-10 V & 4-20mA oil pressure senders. | Provides flexibility for use with multiple sensors and engine types. |
Customisable power up text and images | Allows the installer to change the logo and text on module power up. |
Five key menu navigation | Provides comprehensive front panel module control. |
Backed-up real time clock. | Maintains the settings of the module when power is removed. |
Fuel usage monitor and low level alarms. | Provides information on fuel status at all times. |
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for up to 1 minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 150 mA at 24 V
MAXIMUM STANDBY CURRENT
145 mA at 12 V, 85 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
DIGITAL INPUTS A to H
Negative switching
ANALOGUE INPUTS A & D
Configurable as:
Negative switching digital input
0 V to 10 V sensor
4 mA to 20 mA sensor
Resistive sensor
ANALOGUE INPUTS B & C
Configurable as:
Negative switching digital input
Resistive sensor
OUTPUT A & B (FUEL & START)
10 A DC at supply voltage
AUXILIARY OUTPUTS C, D, E, F, G & H
2 A DC at supply voltage
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 – Front of module when installed into the control panel with the optional sealing gasket.